Home › Cables & fuses

DC voltage drop calculator

Low-voltage DC systems are very sensitive to voltage drop. Enter the current, cable length and size to see how many volts you'll lose before the power reaches your appliance.

A
Distance from the battery (or source) to the load. The return conductor is added automatically.
V

Results

Voltage drop—
Percentage drop—
Voltage at the load—
Power lost in cable—
Round-trip resistance—

The formula

Voltage drop = Current × 2 × Length × ρ ÷ Area ρ (copper, 20 °C) = 0.01724 Ω·mm²/m

The factor of 2 accounts for the current flowing out on the positive cable and back on the negative. If your return path is a vehicle chassis, the drop on that side is usually smaller, but poor chassis connections often add more than you'd expect.

How much voltage drop is acceptable?

Worked example

A 20 A fridge circuit, 5 m from the battery, in 6 mm² cable: 20 × 2 × 5 × 0.01724 ÷ 6 = 0.57 V, or 4.8% at 12 V. That's too much for a fridge, so step up to 10 mm² (2.9%).

Want the calculator to choose the size for you? Use the DC cable size calculator.

Current ratings are guide figures for single-core copper cable. 'Standard PVC' uses conservative values for 70 °C insulation, bundled or enclosed; '105 °C' uses typical marine-table values for high-temperature cable run on its own. Always check the cable maker's rating, and derate for hot spaces such as engine bays.

Frequently asked questions

What is an acceptable voltage drop for 12V?

3% (0.36 V) or less for chargers, inverters, fridges and electronics; up to 10% for lighting.

Does cable length include both wires?

Enter the one-way distance. The calculator doubles it to include the return conductor.

Does temperature affect voltage drop?

Yes. Copper resistance rises about 0.4% per °C, so a hot cable has slightly more drop than this 20 °C calculation shows.