UPS runtime calculator

Enter your equipment's load and the UPS battery details to estimate how long it will keep running in a power cut.

Total power of everything plugged into the UPS. If you only know VA, choose VA.
V
Ah
%

Results

Estimated runtime—
Battery energy—
Battery current—

How it's calculated

Battery current = Load W ÷ Efficiency ÷ Battery bank voltage Runtime = 20 × (Ah ÷ (Current × 20)) ^ k × Usable fraction

UPS batteries are discharged quickly, often in 5–30 minutes, so Peukert's law is used to allow for the lower capacity lead-acid batteries give at high current. The batteries in most UPS units are wired in series, so their voltages add up.

Worked example

A home office UPS with two 12 V 9 Ah batteries (24 V) running a 300 W load at 85% efficiency draws about 14.7 A. That gives roughly 22 minutes, well short of the 37 minutes a simple Ah ÷ A calculation would suggest.

Tips

Frequently asked questions

How long will a 1500VA UPS last?

It depends on the battery, not the VA rating. A typical 1500 VA UPS with two 12 V 9 Ah batteries runs a 300 W load for about 15–20 minutes.

What's the difference between VA and watts?

VA is apparent power. Watts are real power. For computer equipment, watts are roughly 0.6–0.9 × VA. UPS units list both.